Skip to content

Troubleshooting#

Diagnostic Order#

Use the same order for every incident:

  1. Identify the Resource, feature, Material, timestamp, and initiator.
  2. Confirm the selected OPC UA server profile and session state.
  3. Read the current handshake and payload values.
  4. Check the Connect IoT instance status and errors reported.
  5. Check whether the MES transaction committed.
  6. Reconcile MES and machine state before resetting or retrying.

Avoid blind retries

When MachineReplyTimeout expires, the MES operation fails and its transaction rolls back. Reconcile the MES Material state, handshake values, and physical equipment state before resetting or retrying.

Connection and Setup#

Symptom Likely checks Corrective action
No OPC UA session Endpoint reachability, credentials, SecurityPolicy, SecurityMode, and certificate trust Correct the selected profile or server trust and restart the affected instance through the supported Connect IoT lifecycle
Wrong server is used Resource name and the profile selected at setup Apply the canonical Profile Selection Rule, then correct or remove the unintended Resource-specific profile
Base node is incorrect Selected profile's Namespace, IndEqOpcUaBaseNodeId, hierarchy segments, case, and NodeId type Correct Namespace or the MES hierarchy, rerun controller setup, and compare the generated base node with the server address space
MES reports no reply from Connect IoT Automation Controller Instance availability, Automation Manager status, and /IndEq/Automation/ConnectIoTRequestTimeout/ Restore the runtime path and set a timeout appropriate for the validated end-to-end response time
Some nodes are missing Enabled feature versus delivered machine interface and exact OPC UA node names Add or correct the machine nodes, or remove the unsupported feature from the approved scope
Read succeeds but write fails OPC UA role, access level, node writability, and server security identity Grant only the required write permissions to the Connect IoT OPC UA Client

Operation Handshake#

Observed state Meaning Action
Request true, performed false The request is pending, rejected, or failed before the performed signal was written Check Material resolution, EnableAutomationScenarios, MES validation, and Connect IoT diagnostics
Performed true, confirmed false before timeout MES performed the operation within its current transaction and is waiting for the machine Check PLC monitoring and confirmation logic before MachineReplyTimeout expires
MachineReplyTimeout error The machine did not confirm in time; the command failed and the MES transaction rolled back Reconcile MES, handshake, and physical machine state before resetting; then correct the PLC response or configure an appropriate timeout
All bits remain true The reset sequence is incomplete Identify which owner failed to reset its bits and recover in the documented order
Request is never detected The subscription is inactive, no value change occurred, the bit was already high at setup, or the wrong node is configured Verify the subscription, node, initial value, and PLC edge behavior
Operator operation fails while notifying the machine The MES-to-IoT request, performed write, or machine confirmation failed Check the operation event, ConnectIoTRequestTimeout, MachineReplyTimeout, Resource automation scenarios setting, OPC UA write result, and hybrid-station PLC behavior

See Automation Timeout Settings for the supported timeout paths and defaults.

Material and FIFO#

Symptom Checks
Material not found Exact MES Material name, whitespace/case, Material system state
Empty name is rejected IndEqAutomationOperationAllowFIFO is false or missing. This is expected when explicit identification is required
Wrong Material selected by FIFO Queue/in-process ordering, eligibility rule. Prefer explicit Material names where deterministic selection is critical
MES rejects resolved Material Review the standard Track In, Track Out, or Abort preconditions and current Material state

Recipe Download#

Symptom Checks
No recipe is resolved Recipe Management Enabled, RecipeContext, Material/Product/Step/Resource context, and Recipe state/version
Parameter node not found Exact MES Parameter name, sub-recipe display name, case, and base node
OPC UA write returns bad status Access rights, target data type, value range, node state, server diagnostics
Machine receives wrong value MES recipe version, parameter value, conversion precision, sub-recipe mapping

Data Collection#

Symptom Checks
No data is posted Request bit, Material, open Data Collection Instance, expected Parameter list, read status
“No data received” or parse error Empty nodes, bad OPC UA status, incompatible text/numeric/Boolean/date value, wrong configured type
Reading rejected PostDataReadingNumber, configured reading range, mandatory Parameters, limits, instance state
Values stored under wrong Material Explicit Material name or FIFO resolution and Resource/Step context

State Synchronization#

Error Cause Action
Resource has no state model The Resource does not have a state model assigned Assign the correct state model and initial state to the Resource
No state mapping found No direct match and IndEqResourceStateResolution did not resolve Add/correct the Resource + machine state mapping
Mapped MES Resource state is invalid MESResourceState does not name a state in the Resource model Correct the mapping or state-model configuration
Transition is not permitted The Resource state model does not contain a valid runtime transition to the resolved target state Correct the state mapping or add the required Resource state transition
Unexpected state-change reason Check whether State.Reason contains a value and whether the selected transition has a default reason MES applies the supplied reason when present; otherwise it uses the default reason configured for the transition